AC Power - Sun Fire Redundant Transfer Switch

Redundant Transfer Switch

Servers: Sun Fire 6800, E6900
Cabinets: Sun Fire Cabinet

300-1396
200-240VAC   47/63Hz   24A

LED STATUS DESCRIPTION
Left Green On
Off
Flashing
AC present
AC not present or below specification
AC above specification
Middle Green On
Off
Flashing
Relay energized
Relay de-energized and RTS is installed
Relay de-energized and RTS is not installed
Right Amber On
Off
Fault
Normal

Sun Fire 3800-6800 Codename: Serengeti
Sun Fire E6900 Codename: Amazon 6

Notes

  1. The Redundant Transfer Unit abbreviation is RTU.
  2. The Redundant Transfer Switch abbreviation is RTS.
  3. The front and rear locations are abbreviated F and R.
  4. Chassis labels include the abbreviated name, location, and number.
  5. Two totally independent AC power sources are needed for input power redundancy. The power sources must be derived from independent power company utility feeds, and Sun recommends that each be backed up with an online UPS. The power sources are not independent if they are only distinguished by having separate circuit breakers.
  6. In configurations with two independent AC power sources, there will be four cables to connect, two on the front, and two on the rear of the system. Connect RTS 2 (front) and RTS 1 (rear) to one power source, and RTS 3 (front) and RTS 0 (rear) to the other power source:
  7. In configurations with only one AC power source, there will be two cables to connect, one on the front (on the left), and one on the rear of the system (on the left). These are the default RTS units, RTS 2 and RTS 0 respectively:
  8. Connecting the alternate RTS units to outlets that use the same power source as the default RTS units is not supported and will adversely affect reliability.

References

  1. Sun Fire Systems Service Manual, 805-7363.
  2. Sun Fire 6800 System Installation Guide, 805-7375.
  3. Sun Fire Cabinet Installation Guide, 806-2942.
  4. Redundant Transfer Switch Installation Guide, 806-4716.
  5. Sun Fire 6800 System and Sun Fire Cabinet Rackmount Placement Matrix, 816-2062.
  6. Sun Fire E4900/E6900 Service Manual, 817-4120.